Surge arrestor V20, 1-pole + NPE and remote signalling, 280 V

Item no. 5095331 | EAN 4012196163014

  • 5-year warranty
  • Underwriters Laboratories Inc., USA + CSA, Canada
  • Protection device to DIN EN 61643-11 or IEC 61643-11
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • EurAsian Conformity
  • Transition from LPZ 1 to LPZ 2
  • Österreichischer Verband für Elektrotechnik, Austria
  • Regulatory Compliance Mark – Declaration of Conformity for Australia/New Zealand
  • Verband der Elektrotechnik, Elektronik, Informationstechnik e.V., Germany
  • Installation electrotechnical expertise
  • KEMA-KEUR, Netherlands
  • Remote signalling

Surge arrestor, type 2

• For surge voltage protection equipotential bonding to VDE 0100-443 (IEC 60364-4-44)
• Discharge capacity to 40 kA (8/20) per pole through high-performance varistors
• Modular connectable arrestor with cut-off unit and visual status display
• Locking mechanism with vibration protection and voltage keying
• Plastic to UL 94 V-0
• The remote signalling variants (FS) have a potential-free changeover contact for remote signalling

Application: Equipotential bonding in main and sub-distributions.

All types

All types

Types Highest
continuous
voltage
AC
Pole
version
Protec-
tion
rating
Item no. Quantity SSU
V20-1+NPE+FS-280 280 V 1+N/PE IP20 5095331
1 piece
Surge arrestor V20, 1-pole + NPE and remote signalling, 280 V
Surge arrestor V20, 1-pole + NPE and remote signalling, 280 V

Surge arrestor V20, 1-pole + NPE and remote signalling, 280 V

Item no. 5095331

Data sheet, 0.23MB, pdf
Download

Connectivity options

SPD to EN 61643-11 Type 2
SPD to IEC 61643-11 Class II
SPD to UL 1449 Type 4
Nominal voltage AC (50/60 Hz) 230 V
Maximum continuous voltage AC 280 V
Nominal discharge current (8/20 µs) 20 kA
Maximum discharge current (8/20 μs) 40 kA
Arrestor surge current (8/20 µs) [total] 60 kA
Protection level [L-N] 1.3 kV
Combined voltage protection level [L-PE] 1.5 kV
Residual voltage [L-N] @ 1 kA 0,8 kV
Residual voltage [L-N] @ 5 kA 1,0 kV
Max. mains-side overcurrent protection 160 A gL/gG
Short-circuit withstand for max. mains-side overcurrent protection 50 kA eff
Operating temperature range -40 - +80 °C
Protection rating IP20
Approvals UL
FM contacts Changeover
Switching power AC 230 V; 0,5 A
Switching power DC 230 V; 0,1 A / 75 V; 0,5 A
Connection cross-section, FM terminals 0,5 - 1,5 mm²
Connection cross-section, FM terminals 21 - 16 AWG
Conductor cross-section, flexible (fine-wire) 1.5 - 35 mm²
Conductor cross-section, rigid (single wire/multi-wire) 1.5 - 35 mm²
Conductor cross-section, flexible (fine-wire) 16 - 2 AWG
Conductor cross-section, rigid (single wire/multi-wire) 16 - 2 AWG
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min. 440 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s 335 V
TOV voltage [N-PE] ‒ withstand mode ‒ 200 ms 1200 V

Dimensions

Installation dimensions (LxWxH) 90x35,6x78,5 mm
Size 2 part units
Minimum distance 1.5 mm
3D data
Invitation to tender text

Invitation to tender text

V20-1+NPE+FS-280 / 5095331
Download
Downloads

Data sheet

V20-1+NPE+FS-280 / 5095331, 0.23MB, pdf
Download

Catalogues & Flyers

MCF Compact, V50, V20: The new team to combat surge voltages, 0.80MB, pdf
Download
Lightning protection guide, 25.41MB, pdf
Download

Declarations of conformity