LightningController - MCF50-NAR-TT

Item no. 5096975 | EAN 4012196608782

5096975 / MCF50-NAR-TT
3+N/PE
12.5 kA
no
255
IP20
Product description

Product description

Combination arrester, type 1+2, for mounting on 40 mm busbars, for TN-S and TT systems

• Protection level ≤1.5 kV to protect the terminals
• Lightning protection equipotential bonding according to VDE 0185-305 (IEC 62305)
• Lightning current arresting capacity up to 50 kA (10/350) 3+NPE
• Fulfils the requirements of VDE 0100-534 (IEC 60364-5-53)
• Line follow current quenching up to 50 kA and max. backup fuse up to 160 A gL/gG
• Spark gaps for use in the pre-meter area according to VDE-AR-N 4100

Application: Building with lightning protection or outside cable infeed.
  • Verband der Elektrotechnik, Elektronik, Informationstechnik e.V., Germany
  • 5-year warranty
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • RoHS-conformant
  • 230/400 V system
  • Combination protection device made of type 1 and type 2
  • Transition from LPZ 0 to LPZ 2
  • Halogen-free; without chlorine, fluorine and bromine
Technical data

Technical data

Approvals VDE
Cable type for surge protection devices Power cable AV
Conductor cross-section, flexible (fine-wire), max. 2 AWG
Conductor cross-section, flexible (fine-wire), max. 35 mm²
Conductor cross-section, flexible (fine-wire), min. 7 AWG
Conductor cross-section, flexible (fine-wire), min. 10 mm²
Conductor cross-section, rigid (single-wire/multiwire), max. 35 mm²
Conductor cross-section, rigid (single-wire/multiwire), max. 2 AWG
Conductor cross-section, rigid (single-wire/multiwire), min. 7 AWG
Dimension 255V
Follow current quenching capacity (eff) [N-PE] 0,1 kA
Housing material PA UL 94 V-0
Installation type Bus bar 40 mm
Lightning surge current (10/350 μs) 12,5 kA
Lightning surge current (10/350) 50 kA
Maximum back-up fuse 160 A
Maximum continuous voltage (L-N) 255 V
Maximum continuous voltage (N-PE) 255 V
Maximum continuous voltage AC 255
Maximum discharge current (8/20 μs) 50 kA
Maximum discharge current (8/20 μs) [L-N] 50 kA
Maximum discharge current (8/20 μs) [N-PE] 100 kA
Network form TN-S, TT
Nominal discharge current (8/20 µs) 20 kA
Nominal discharge current (8/20 µs) [L-N] 20 kA
Nominal discharge current (8/20 µs) [N-PE] 80 kA
Nominal voltage AC (50/60 Hz) 230 V
Operating temperature, max. 80 °C
Operating temperature, min. -40 °C
Pole version 3+N/PE
Protection rating IP20
Remote signalling no
Response time <100 ns
Signalling on device Visual
SPD to EN 61643-11 Type 1+2
SPD to IEC 61643-1 Class I+II
TN network form yes
TN-C-S network form yes
TN-S network form yes
Torque 3,5 Nm
TOV voltage [N-PE] ‒ withstand mode ‒ 200 ms 1200 V
TT network form yes
Version for 3+NPE

Dimensions

Height 109 mm
Length 226 mm
Width 50 mm

Connectivity options

Arrester surge current (8/20 µs) [total] 80 kA
Combined voltage protection level [L-PE] 2,5 kV
Conductor cross-section, rigid (single-wire/multiwire), min. 10 mm²
Max. mains-side overcurrent protection 160 A
Protection level [L-N] ≤1,5
Short-circuit resistance for max. mains-side overcurrent protection 50 kA eff
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min. 442 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s 440 V
All types

All types

Types Pole version Lightning surge current (10/350 μs) Remote signalling Maximum continuous voltage AC Protection rating Item no. Quantity SSU
MCF50-NAR-TT 3+N/PE 12.5 kA no 255 IP20 5096975
1 piece
Accessories

System accessories

Products Types Item no. Quantity SSU
Voltage tap for MCF-NAR series Voltage tap for MCF-NAR series MCF-NAR-SMG 5096900
1 piece
Downloads

Download

Declaration of conformity MCF50-NAR-TT / 5096975 , 0.13MB , pdf
Download

Download
Download

MCF50-NAR-TT / 5096975
Download