Upper part MCF-P-NPE

Item no. 5096935 | EAN 4012197505158

5096935 / MCF-P-NPE-0
N/PE
255 V
IP20
Product description
Product description
Spare upper part NPE

• Matches the MCF-P series
• Pluggable for quick and easy exchange
• Clear coding to avoid incorrect use
• Protection level < 1.5 kV
• Lightning current arresting capacity 100 kA (10/350)
* Complete = Plug-in arrester and base
  • 5-year warranty
  • Protection device to DIN EN 61643-11 or IEC 61643-11
  • Transition from LPZ 0 to LPZ 2
  • 230/400 V system
  • Packaging without plastic
  • Packaging made entirely from recycled cardboard
  • CO₂ footprint (PCF)
Technical data

Technical data

Blow-out no
CO2 Footprint (GWP) Cradle-to-Gate 0,404 kg CO2e / 1 Piece
DC network form no
Dimension 255V
Follow current quenching capacity (eff) [N-PE] 0,1 kA
Height 45 mm
Humidity, max. 95 %
Humidity, min. 5 %
Installation type On basic element
Integrated back-up fuse no
IT network form no
Length 66 mm
Maximum continuous voltage (N-PE) 255 V
Maximum continuous voltage AC 255 V
Maximum discharge current (8/20 μs) [N-PE] 100 kA
Nominal discharge current (8/20 µs) [N-PE] 100 kA
Nominal voltage AC (50/60 Hz) 230 V
Other network form no
Permitted temperature range, max. 70 °C
Permitted temperature range, min. -40 °C
Pole version N/PE
Protection rating IP20
Signalling on device Visual
SPD to EN 61643-11 Type 1+2
SPD to IEC 61643-1 Class I+II
Suitable for outdoor use no
Test class, type 1 yes
TN network form yes
TN-C network form no
TN-C-S network form yes
TN-S network form yes
TOV voltage [N-PE] ‒ withstand mode ‒ 200 ms 1200 V
TT network form yes
Width 36 mm
All types

All types

Types Pole version Maximum continuous voltage AC Protection rating Item no. Quantity SSU
MCF-P-NPE-0 N/PE 255 V IP20 5096935
1 piece
Downloads

MCF-P-NPE-0 / 5096935
Download